PRODUCTS

Piston Flow System (UL/FM)

Piston Flow System (UL)

Conventional installation of the clean agent HFC-227ea-based fire extinguishing system is constrained by the size of protected area and distance for agent delivery. This is due to the fact that for such protected area, the quantity of agent becomes insufficient for fire extinguishing when HFC-227ea agent and the propelling Nitrogen are contained in a single cylinder and pressurized to about 25 bar.

 

To overcome this limitation, in 1998 Masteco Industry, Co., Ltd. started the development of HFC-227ea PFS in which a separate cylinder is added to contain the Nitrogen. The two cylinders are interconnected by suitable pipes and valves such that during discharge the high-pressure Nitrogen superpressurizes and pushes the extinguishing agent like a gas piston in order to sustain the required pressure and agent mass flow rate. This configuration enables the system to discharge more than 95% of the extinguishing agent over a wider protected area requiring longer agent flow distances within 10 seconds.

MASTECO
173, Aenggogae-ro 490beon-gil, Namdong-gu, Incheon, Korea 21694
  • TEL+82 2 785 1301(Sales)+82 32 811 1301(Incheon Factory)+82 43 883 3615(Gamgok Factory)
  • FAX+82 2 785 1313(Sales)+82 32 811 1305(Incheon Factory)+82 43 883 3616(Gamgok Factory)

COPYRIGHT © 2017 MASTECO. ALL RIGHTS RESERVED.